Chillers, CRACs and the AIM Act: What EHS Teams Must Do Before Retiring Cooling Equipment in 2027

TL;DR for EHS managers: Since January 1, 2026, owners and operators of HFC equipment holding 15 pounds or more of refrigerant must calculate leak rates, repair within 30 days and keep records for three years under EPA's Emissions Reduction and Reclamation (ER&R) rule. From January 1, 2027, new cooling systems in the data center and IT equipment subsector must use refrigerants with a GWP of 700 or less. Existing equipment can keep running, but every leaking unit that ends up on a retrofit or retirement plan becomes a waste and compliance project: refrigerant recovery, metal scrap, invoices and records.
What applies today (since January 1, 2026)
- Scope. Leak repair covers appliances with a charge of 15 lb or more of a refrigerant containing an HFC or a substitute with a GWP above 53; residential and light commercial AC is excluded (EPA fact sheet, Jan. 2026). Under the older Clean Air Act section 608 program, the threshold was 50 lb and applied to ozone-depleting refrigerants.
- Leak rate thresholds. 30% for industrial process refrigeration, 20% for commercial refrigeration, 10% for comfort cooling and other appliances. A leak rate must be calculated each time refrigerant is added.
- 30-day clock. Leaks above the threshold must be repaired within 30 days (120 days if an industrial process shutdown is required), with initial and follow-up verification tests.
- Retrofit or retire. If you choose not to repair, or repairs fail, a retrofit or retirement plan is due within 30 days and the work must generally be completed within one year.
- Chronic leakers. Appliances that leak 125% or more of their full charge in a calendar year must be reported to EPA by March 1 of the following year, so March 1, 2027 for 2026 leaks.
- Records. Kept for three years, on paper or electronically (EPA).
- Reclaimed refrigerant. Since January 1, 2026, refrigerant containing more than 15% virgin HFC by weight cannot be sold or reported as reclaimed (Baker Botts).
What changes on January 1, 2027
- Data centers: GWP 700 for new systems. EPA's Technology Transitions table sets a 700 GWP limit for the subsector "data centers, computer room air conditioning and IT equipment cooling", effective January 1, 2027 (EPA, restrictions by sector). R-410A (GWP 2,088) and R-134a (GWP 1,430) are above that limit (DC Build X; G&D Chillers). The May 26, 2026 reconsideration rule changed other subsectors but, as of November 2026, the data center rows still show January 1, 2027 (Advanced Air System).
- Existing equipment is not banned. The rule does not restrict the continued use of existing systems (EPA fact sheet). Expansions are the trap: EPA can treat increasing a system's capacity as a new installation (G&D Chillers).
- Automatic leak detection. Large commercial and industrial process refrigeration systems (1,500 lb or more) installed between 2017 and 2026 must have automatic leak detection by January 1, 2027 (EHSTracks; SkillCat).
- Manufacturing sites: the May 2026 rule pushed some industrial process chiller dates, for example to January 1, 2030 for certain semiconductor chillers (Federal Register; FluoroFusion). The leak repair rules were not relaxed; EPA has only signaled it intends to revisit them (Holland & Knight).
Why this is a waste problem, not only an HVAC problem
A retirement plan ends with equipment leaving the site. Before disposal, refrigerant must be recovered by certified technicians; the recovered gas is either reclaimed by an EPA-certified reclaimer or destroyed, and the units themselves carry copper, aluminum and steel. Inspectors start with the paperwork: iSi Environmental reports that an EPA inspector's first request is the refrigerant service tickets and leak-rate calculations for every appliance above 15 lb. If those tickets, recovery records and scrap invoices live in three different places, you cannot prove where the refrigerant went or what the metal was worth.
[[button-1]]
The 7-point checklist
- Inventory every appliance at 15 lb or more, by site and circuit, with refrigerant type, full charge and subsector.
- Check every 2026 service ticket for a leak-rate calculation after each top-up.
- Flag chronic leakers now to prepare the March 1, 2027 report.
- Freeze purchase orders for non-compliant data center cooling that will not be installed before January 1, 2027.
- Write disposal into retirement plans: who recovers the refrigerant, which reclaimer or destruction facility, which scrap outlet.
- Ask for weights and certificates: pounds of refrigerant recovered per unit, scale tickets for scrap, certificates of reclamation or destruction.
- Reconcile invoices: recovery, haul-away and scrap credits should match the contract and the equipment list.
Where Wastetide fits
Wastetide reads waste and service invoices, contracts and registers to produce audit-ready data per site and stream (automated, compliant data), flags gaps between billed and contracted prices (contract monitoring) and estimates the value of end-of-life equipment so copper and aluminum are sold, not given away (material identification). Related reads: lithium-ion UPS battery waste, how to audit a waste hauler invoice and our waste RFP template.
[[button-2]]
FAQ
Which equipment is covered by EPA's 2026 refrigerant leak repair rule?
Appliances with 15 lb or more of a refrigerant containing an HFC, or a substitute with a GWP above 53, except residential and light commercial air conditioning and heat pumps.
Do I have to replace my existing data center chillers or CRACs in 2027?
No. The GWP 700 limit applies to new systems installed from January 1, 2027. Existing equipment can keep operating and be serviced, but it remains subject to leak repair rules.
How fast must a leak be repaired?
Within 30 days of adding refrigerant to an appliance above its leak rate threshold, or 120 days if an industrial process shutdown is required, followed by verification tests.
What is a chronically leaking appliance?
One that leaks 125% or more of its full charge in a calendar year. It must be reported to EPA by March 1 of the following year.
How long must refrigerant records be kept?
Three years, on paper or electronically.
Sources: U.S. EPA (ER&R leak repair fact sheet, Jan. 2026; Technology Transitions restrictions by sector); Federal Register, May 26, 2026; Holland & Knight; Baker Botts; iSi Environmental; EHSTracks; SkillCat; DC Build X; G&D Chillers; Advanced Air System; FluoroFusion. Image: U.S. EPA, refrigerant tanks staged for reclamation, 2012, public domain, via Wikimedia Commons. Informational, not legal advice; check state rules (e.g., California) which may be stricter.